Dimming actuator, 4-gang for Gira One

Ideal for dimming high-voltage LEDs.

The Gira dimming actuator 4-gang for Gira One is designed for switching and dimming a large number of different light sources. It features a simplified DRA wiring concept with high-quality connection terminals on both sides of the housing, enabling quick and safe installation. In a compact design of only four modular widths, the dimming actuator provides a total of four outputs for the separate control of lighting circuits of up to 225 W each.

The product is particularly suitable for the activation of modern high-voltage LEDs, with up to 200 W dimmable per output. Gira System 3000 power boosters are also available for even higher power levels.

  • Actuator for switching and dimming light bulbs, HV halogen lamps, dimmable HV LED lamps and much more.
  • Automatic or manual selection of dimming principle according to load.
  • Open-circuit, short-circuit, and excess temperature-proof.
  • Power extension using power boosters.
  • Manual operation of the outputs.
  • Programming and start-up using the Gira Project Assistant (GPA) version 5.0 or higher
  • Encrypted data transfer between the Gira One devices.

OneKNX DRA dimm.act. 4-g Std

KNX medium:
TP256

Rated voltage:
AC 110 to 230 V, 50/60 Hz

Max. connected load (AC 230 V) per channel
Light bulbs:
20 to 225 W
HV halogen lamps:
20 to 225 W
Wound electronic transformer:
20 to 210 VA
Tronic transformer:
20 to 225 W
Wound transformer with NV-LED:
20 to 100 VA
electronic transformer with NV-LED:
typically 20 to 200 W
HV LED lamps:
typically 1 to 200 W
Compact fluorescent lamp:
typically 20 to 150 W

Connected load (AC 110 V) per channel
Light bulbs:
20 to 110 (120) W
HV halogen lamps:
20 to 110 (120) W
Wound electronic transformer:
20 to 110 VA
Tronic transformer:
20 to 110 (120) W
Wound transformer with NV-LED:
20 to 50 VA
electronic transformer with NV-LED:
typically 20 to 50 (100) W
HV LED lamps:
typically 1 to 18 (100) W
Compact fluorescent lamp:
typically 20 to 40 (75) W

Connections
KNX:
Connection and junction terminal
Load:
Screw terminals

Connection cross section:
Max. 4 mm²