Name |
Port type |
Description |
Trigger |
Bool |
Notification node trigger. If a “1” is received at this input, the notification is sent to the output. |
Title |
String |
A fixed text for the title of the notification can be entered here.
Alternatively, the text for the title can also be received via the input as a 14-byte text by means of a KNX telegram or variable data point. |
Content |
String |
A fixed text for the content of the notification can be entered here.
Alternatively, the text for the content can also be received via the input as a 14-byte text by means of a KNX telegram or variable data point. |
LED check |
|
Controls Gira G1’s LED. Selection from the following options:
- Fixed LED colour
- Single LED colour value
- Input for each colour |
LED colour |
|
Defines the colour for Gira G1’s LED. There is a choice of red, green, yellow, blue, magenta, turquoise, and white. “Off” means the LED is switched off. “No change” means the LED’s status is not changed. |
LED colour value |
Byte |
The colour of the LED can be controlled via the input. The following values are used: 0 - Black (Off) 1 - Red 2 - Green 3 - Yellow 4 - Blue 5 - Magenta 6 - Turquoise 7 - White
|
Input for each colour: Red LED Green LED Blue LED |
Binary |
The LED’s colour can be determined using the three individually controllable inputs. The following values are used:
Red |
Green |
Blue |
Colour |
0 |
0 |
0 |
Black (Off) |
1 |
0 |
0 |
Red |
0 |
1 |
0 |
Green |
1 |
1 |
0 |
Yellow |
0 |
0 |
1 |
Blue |
1 |
0 |
1 |
Magenta |
0 |
1 |
1 |
Turquoise |
1 |
1 |
1 |
White |
|
Switch on screen |
Bool |
Gira G1’s screen can be switched on via the input. If this input has a “1”, the screen will be switched on when the next message is received. |
Time stamp |
|
The time stamp can either be generated internally (by the Gira L1 or Gira X1) or received externally via the KNX bus. |
External time stamp |
DateTime |
This input can be used to receive the time stamp via a KNX telegram. |
Use Reset |
|
The logic node can be reset via the “Reset” input, which can be optionally activated. |
Reset |
Binary |
If a “1” is received at this input, the logic node is reset. |
Use consecutive texts |
|
If a notification is too long to be sent in a KNX telegram, long notifications can be sent in successive text fragments. These text fragments are collected in the Gira G1 and then displayed next to each other. |
Time span for merging texts |
|
This is where you set the time span that should be provided for collecting the text fragments. |